Fixed CO2 Fire Suppression System
- Code:
- PYR-CO2
- Manufacturer:
- Mobiak
Carbon dioxide is a colourless, tasteless, odourless and inert gas. Its use causes no damage at all.
Send us the products you are interested in, and we will call you with a quote.
Description
Carbon dioxide is a colourless, tasteless, odourless and inert gas. Its use causes no damage at all (unlike water or dry powder, whose use in many cases causes damage); it is harmless to most materials, does not contaminate food, is not corrosive and is a poor conductor of electricity. After extinguishing a fire it evaporates completely and leaves no residue at all. It can therefore be used safely in areas with sensitive electrical and electronic installations, valuable works of art, paintings or manuscripts, flammable liquid stores, electrical substations, ovens and furnaces.
Because it causes asphyxiation, it is unsuitable for areas where people or animals are present. The three-dimensional action of carbon dioxide means that it can fight fires both vertically and horizontally. Its rapid movement allows it to get past any obstacle through an opening and to reach inaccessible and hidden spots. Carbon dioxide is a stable commercial product with many other uses, and it is available worldwide. The fixed suppression system can operate either automatically or manually, and automatic control can be achieved mechanically and pneumatically, or electronically, or by a combination of these, depending on the conditions. Carbon dioxide is stored at room temperature in steel cylinders. The pressure varies with temperature and at 21 °C is approximately 59 bar. A multiple cylinder bank can be built.
SYSTEM DESCRIPTION
Single- or multiple-cylinder systems are used, depending on the volume of the areas to be protected. In a multiple-cylinder system, the pilot cylinder is used to activate the system's cylinders. The pilot cylinder is activated automatically by a pyrotechnic actuator, which is fired by the system's fire detection and extinguishing control panel. The panel receives the command from a detection system made up of pairs of heat detectors and smoke detectors. It is activated manually either by pushing the plunger of the valve or by a remote manual activation button. The valve of the pilot cylinder is connected to the valve of the system's 1st cylinder by a high-pressure EPDM flexible hose. In practice, when the pilot cylinder is activated, its propellant gas pneumatically actuates the valves of the system's main carbon dioxide cylinders (the valves of the system's main cylinders are connected by high-pressure EPDM flexible hoses). As soon as the system's main cylinders are activated, the extinguishing agent is driven through high-pressure EPDM flexible hoses into the system manifold, from where it is led to total flooding or local application nozzles.
THE SYSTEM INCLUDES
Cylinders
- Certified carbon dioxide cylinders of 16 L (12 kg), 40 L (30 kg), 50 L (35 kg), 67.5 L (45 kg), 67.5 L (50 kg) and 80 L (60 kg), with an automatic, manual or pneumatic activation valve, a protection disc and heavy-duty brackets.
- Certified 3 L (2 kg) pilot cylinder with an automatic, manual or pneumatic activation valve and a heavy-duty bracket.
Manifold components
– Manifold pipe, 1¼” to 3” in diameter
– Manifold tee, 1¼” to 3” in diameter
– Manifold end cap, sizes 1¼” to 3”
– Manifold reducer, 1¼” => ¾”, 2” =>1”, 2½” =>1½”, 3”=>2”.
– ¾” non-return valve.
EPDM flexible hoses
- High-pressure EPDM flexible hose connecting the pilot cylinder to the valve of the first cylinder in a multiple-cylinder system
- High-pressure EPDM flexible hose connecting the cylinders of a multiple-cylinder system
- High-pressure EPDM flexible hose connecting the system cylinders to the manifold non-return valve
- High-pressure EPDM flexible hose connecting the cylinder of a single-cylinder system to the nozzle network
Other components
– Nipple (3/8” – 3/8”) for connecting the EPDM flexible hoses to the valves of the system cylinders
– 3/8” plug for sealing the valve outlet of the pilot cylinder and of the last cylinder of the system
– Local application nozzles
– Total flooding nozzles
Fire detection
- Certified four-zone control panel
- Audible and visual sounder
- System manual activation button
- Extinguishing abort button
- Heat detectors (fixed-temperature or rate-of-rise)
- Smoke detectors
- STOP GAS sign
CERTIFICATES
ISO 9809 – 1 EN 1964 – 1, π 99/36/EC
CE FOR PILOT CYLINDER 97/23/EC (TUV)
MANIFOLD TESTS AT 300 bar BY EBETAM S.A.
CE FOR VALVE (BV) CE 0062