Every shop needs the fire protection measures the law sets: fire extinguishers, emergency lighting and safety signs and, above a certain size, fire detection. A fire protection certificate is needed when the shop's operating licence or notification requires one, or when it is in risk category C. It is issued by the Fire Service on an engineer's application and is valid for five years.
Which rules apply
- The procedure, that is when a certificate or a study is needed and how it is filed: Fire Service Ordinance 13/2021 (Ministerial Decision 69019 Φ.700.13, Gazette B' 5519/2021).
- The measures depend on when the building permit was applied for. For buildings applied for before 17 February 1989, Fire Service Ordinance 8/2016 (Ministerial Decision 74088 Φ.700.8, Gazette B' 165/2017) applies. For newer ones, Presidential Decree 71/1988 or, for buildings put up after 7 August 2018, Presidential Decree 41/2018.
- Restaurants and cafés, where the public sits, have rules of their own. See fire safety for restaurants and commercial kitchens.
When a certificate is needed
Ordinance 13/2021 sorts shops into risk categories, mainly by floor area. For a shop that operates freely, without a licence or notification that calls for a certificate:
| Category | Shops | What is filed |
|---|---|---|
| A | Up to 1,000 m², and outdoor shops | Nothing is filed, but the legal measures still apply |
| B | 1,000 to 2,500 m², and high-risk shops up to 750 m² | The fire protection study is filed for the record |
| C | Over 2,500 m², basements with a theoretical occupancy over 150 people, and high-risk shops over 750 m² | Fire protection certificate |
When the licence or notification for the activity calls for a certificate, it is needed in any category.
How the certificate is issued
- Who applies: a graduate engineer who is a member of the Technical Chamber of Greece (TEE), online, through the "E-Adeies / Fire Service approvals" platform.
- What is needed: the engineer's sworn statement; the owner's or operator's sworn statement on maintenance of the equipment and staff training; the recognised company's sworn statement on the extinguishers it supplied, serviced or recharged; and the fee.
- Validity: five years. Renewal is applied for at least two months before expiry.
- Temporary certificate: once only and for up to six months, for a business that has not finished its fixed hydrant network or automatic suppression system.
How many extinguishers
Ordinance 8/2016 calls for dry powder or water-based extinguishers rated at least 21A-113B-C:
- one per 150 m² of gross floor area, or one per 100 m² in high-risk shops;
- fractions round to the nearest whole number, and there must be at least two;
- in plant rooms and boiler rooms, CO2 extinguishers rated at least 55B-C, also at least two.
For example, a 400 m² shop needs 400 / 150 = 2.67, that is three extinguishers. Presidential Decree 41/2018 has the same rule for new buildings. Which type suits which space is in the guide Types of fire extinguishers.
Detection, lighting and signs
- Fire detection and a manual fire alarm are needed in shops with three or more floors of main use (counting the basement), with a total covered area over 1,000 m², and in high-risk shops. See fire detection systems.
- Emergency lighting along escape routes and at emergency exits. See emergency lighting.
- Safety signs along escape routes, at emergency exits and on fire-fighting equipment.
- Escape plans from three floors and 300 people.
The fire protection study
The study describes the shop's fire protection measures. For shops under Ordinance 8/2016 it is drawn up by a qualified engineer, on the template published in the same Gazette. It is not needed for outdoor shops, nor for shops that need no certificate, unless they ask for deviations. Where a certificate is required, an approved study is required too.
Afterwards: maintenance and training
The owner or operator is responsible for the fire protection equipment. Extinguishers are serviced every year by a recognised company, as the guide Fire extinguisher servicing and recharging describes, and staff are trained to use them.
How we help
Pyrosvesi draws up your business's fire protection study, in-house or with qualified partners, supplies and installs what it specifies, and maintains the extinguishers and systems. As a recognised company, we also give you the sworn statement about the extinguishers that the certificate requires. Call us on +30 210 81 00 613.
Sources (in Greek)
- Fire Service Ordinance 13/2021, Gazette B' 5519/2021: certificate, study, risk categories (Annex D).
- Fire Service Ordinance 8/2016, Gazette B' 165/2017: fire protection measures for shops.
- Presidential Decree 41/2018, Gazette A' 80/2018: building fire protection code.
- National Register of Procedures (mitos.gov.gr): the active fire protection certificate.